8,
Sadovskogo Str. Poltava,
36034, Ukraine
Tel: +38 (0532) 66-86-45
Fax: +38 (0532) 66-86-45
cell: +38 050 52-10300
cell: +38 067 166-3333
Oil Purification Specialist
P.O. Box 898
Manchester, CT 06045
Direct Phone: 603-881-4197
Direct Fax: 603-881-8237
Mobile: 603-315-9453

The unit is designed for heating, drying and refining of transformer oil from mechanical impurities, water and acids. It is also intended for insulation restoration of current and voltage oil-filled transformers, for solid insulation cleaning of power transformers, for insulation drying of power transformers, transformer oil regeneration with granular synthetic or natural adsorbents, regeneration of granular synthetic or natural adsorbents with vacuum, for regeneration and refining of other types of mineral and synthetic oil.
UVM-6 system is designed for degassing, solid particle removal, nitrogenation and heating of transformer oil, filled into power transformers up to 1150 kW.
The oil processing station can be used for heating of oil filled electric equipment with hot transformer oil, as well as for vacuumizing power transformers.
The UVM-6 can be used for installation, repair and operation of power equipment.
Application of the unit in closed rooms required exhaust ventilation.
Applications
Purifying and drying Transformer Oil in bulk
Vacuum filling of Transformers and Electrical equipment
Drying and Purifying oil in transformers (on and off-line)
Vacuum Drying of Transformers
Benefits
Removes Dissolved Moisture Transformer Oil
Reduces combustible gases and oxygen
Improves oil dielectric values
Improves transformer power factor
Extends oil service life
Extends transformer service life and reliability
|
No |
Specification |
Value |
|
UBM-6 | ||
|
1 |
Capacity, m3/hour - degassing mode - heating/filtration mode |
До 1 6 |
|
2 |
Processed oil parameters: - max gas content by volume. % - max moisture content by weight, g/ton, - filtration, micron |
0,1 10 5 |
|
3 |
Max output oil temperature in heating mode, ºС |
60 |
|
4 |
Max power consumption. kW |
36 |
|
5 |
Max residual pressure in vacuum tank during degassing, Pa |
266 |
|
6 |
Power supply voltage, three-phase at 50Hz, V |
380 |
|
7 |
Dimensions, mm, - length - width - height |
1600 1150 1930 |
|
8 |
Weight. kg |
1100 |