UVM-10-10 transformer oil processing system

The unit is designed for heating, drying and refining of transformer oil from mechanical impurities, water and acids. It is also intended for insulation restoration of current and voltage oil-filled transformers, for solid insulation cleaning of power transformers, for insulation drying of power transformers, transformer oil regeneration with granular synthetic or natural adsorbents, regeneration of granular synthetic or natural adsorbents with vacuum, for regeneration and refining of other types of mineral and synthetic oil.

UVM-10-10 system is designed for degassing, solid particle removal, nitrogenation and heating of transformer oil, filled into power transformers up to 1150 kW

 The oil processing station can be used for heating of oil filled electric equipment with hot transformer oil, as well as for vacuumizing power transformers.

The UVM-10-10 can be used for installation, repair and operation of power equipment.

This system is containerized, with lockable door.

The UVM-10-10 cannot be operated in explosive, toxic or chemically aggressive environments Application of the unit in closed rooms required exhaust ventilation.

Applications

  • Purifying and drying Transformer Oil in bulk

  • Vacuum filling of Transformers and Electrical equipment

  • Drying and Purifying oil in transformers (on and off-line)

  • Vacuum Drying of Transformers

Benefits

  • Removes Dissolved Moisture Transformer Oil

  • Reduces combustible gases and oxygen

  • Improves oil dielectric values

  • Improves transformer power factor

  • Extends oil service life

  • Extends transformer service life and reliability

No

Specification

Value

UVM-10-10

1

Capacity, m3/hour

- degassing mode

- heating and filtration mode

 

10

15

2

Processed oil parameters

- max gas content by volume %,

- max water content by mass, g/t,

- filtration fineness, micron

 

0,1

10

5

3

Max oil output temperature in heating mode, ºC

85

4

Output pressure, MPa

0,4

5

Oil heater power, kW

200

6

Max power consumption, kW

225

7

Max residual pressure in vacuum column in degassing mode, Pa

267

8

Power supply

- voltage, V

- AC frequency, Hz

 

380

50

9

Dimensions, mm

- length

- height

- width

3500

2250

2250

10

Weight, kg

3800