8,
Sadovskogo Str. Poltava,
36034, Ukraine
Tel: +38 (0532) 66-86-45
Fax: +38 (0532) 66-86-45
cell: +38 050 52-10300
cell: +38 067 166-3333
Oil Purification Specialist
P.O. Box 898
Manchester, CT 06045
Direct Phone: 603-881-4197
Direct Fax: 603-881-8237
Mobile: 603-315-9453
The unit is designed for heating, drying and refining of transformer oil from mechanical impurities, water and acids. It is also intended for insulation restoration of current and voltage oil-filled transformers, for solid insulation cleaning of power transformers, for insulation drying of power transformers, transformer oil regeneration with granular synthetic or natural adsorbents, regeneration of granular synthetic or natural adsorbents with vacuum, for regeneration and refining of other types of mineral and synthetic oil.
Oil purification system SMM-5Z is designed for removal of solids and water from lubrication and insulation oils with viscosity less than 70 cSt at 50 °С, with zeolite absorbent and for subsequent regeneration of zeolite directly in the unit.
The unit is used for installation, repairs and operation of oil filled high voltage equipment with voltages up to 500 kV (power transformers, high voltage switches etc). Ambient conditions for operation:
- ambient temperature + 10 to + 35°С;
- atmospheric pressure 84 to 106,7 kPa (26.77 to 31.49 in.hg);
- elevation up to 2000 m;
- fire and explosion proof building.
Applications
Purifying and drying Transformer Oil in bulk
Vacuum filling of Transformers and Electrical equipment
Drying and Purifying oil in transformers (on and off-line)
Vacuum Drying of Transformers
Benefits
Removes Dissolved Moisture Transformer Oil
Reduces combustible gases and oxygen
Improves oil dielectric values
Improves transformer power factor
Extends oil service life
Extends transformer service life and reliability
|
№ |
Specification |
Value |
|
SMM-5Z | ||
|
1 |
Capacity, m3/hour |
5,0 |
|
2 |
Max processed oil temperature in heating mode, оС |
40 |
|
3 |
Oil heater power, kW |
70 |
|
4 |
Maximum mean surface power of the oil heater, W/cm2 |
1,1 |
|
5 |
Processed oil parameters - water content by weight, g/tonn. - filtration fineness, micron |
10,0 5 |
|
6 |
Zeolite regeneration process specifications: - air heater power, kW - steam heater power, kW - steam temperature for steam flushing, Со - air temperature for drying, Со - vacuum pressure, kg/cm2 |
12 30 150 250 (-0,85;-0,95) |
|
7 |
Total absorber volume, liters |
900 |
|
8 |
Rated power consumption, kW |
120 |
|
9 |
Power consumption, kW -oil drying with heating -oil drying without heating -zeolite regeneration (average) |
74 4 15 |
|
10 |
Three phase power voltage at 50 HZ, V |
380 |
|
11 |
Dimensions, mm - length - width - height |
2700 1500 2100 |
|
12 |
Weight (without zeolite), kg Weight(with zeolite), kg |
1550 2350 |